My Cart $-.--
Shop by Category
Quick Order
0
Home HVACR Components Pressure Regulators Evaporator Pressure Regulating Valve ORIT-10-0/50 1-1/4" Port 1-3/8" ODF 0 - 50 PSIG

PARKER HANNIFIN CORP

Pressure Regulating Valve ORIT-10-0/50 1-1/4" Port 1-3/8" ODF 0 - 50 PSIG

PART ORIT10-0/50-1-3/8ODF
MFG 901166
Calculating price...
QUANTITY

About this item

  • ORIT has high-side pilot for improved temperature control and low pressure drop
  • ORIT is normally open to allow system evacuation without a manual operator
  • Range of adjustable settings up to 150 psi
  • Optional solenoid feature to close valve during defrost

The Parker Sporlan type (S) ORIT evaporator regulating valves have a brass body and extended copper connections. They are available with a range of adjustable settings and pressure tap. The primary function of these valves, referred to as EPR valves, is to prevent the evaporator pressure from falling below a predetermined value or setting. Each valve is factory tested to ensure positive leak-free performance.

Instruction/Installation Manual
Instruction/Installation Manual
Video Link
Video Link
Catalog
Catalog
Brand PARKER HANNIFIN CORP
Series ORIT Series
Nominal Size 1-3/8 in
End Type Solder
Pressure Rating 0 to 50 psi
Temperature Rating -40 to 155 deg F
Body Material Brass
Height 28.42 in
Additional Information Tetraseal, 40 Mesh Insertable Strainer, 1.218 in Port